Description
DO YOU NEED ADDITIONAL CONFIGURATIONS?
For other configurations contact the sales representative
TECHNICAL SPECIFICATIONS
Transducer
Coil length: 15 … 50 cm
Cord diameter: 7.2 ±0.2 mm
Fastening: bayonet holder
Weight: from 150 to 500 g
Jacket material: Polyphenylene and thermoplastic elastomer
Electrical characteristics for model without integrator
Nominal output rate: 120 mV / kA @ 60 Hz (RMS values)
100 mV / kA @ 50 Hz (RMS values)
Max measurable current: 600 A with 15 … 28 cm coil length
2500 A with 29 … 41 cm coil length
5000 A with 42 … 50 cm coil length
Coil resistance: 170 … 690 Ω
Accuracy: Class 1-A1 according to IEC 61869-10
Frequency: 50/60 Hz
Maximum primary voltage: 600 V CAT IV, Service Entrance
Pollution degree: 3, Uncontrolled Environment
Insulation test voltage: 7400 VRMS / 5 s
Electrical characteristics for model with integrator
Power voltage: 4 … 26 VDC
Max consumption: 5 mADC
Nominal output rate: 333 mV / FS (RMS values)
FS changes according to the model: 200, 250, 600, 1000 A
Positioning error: Better than ±1% of reading
Frequency: 50/60 Hz
Maximum primary voltage: 600 V CAT IV, Service Entrance
Pollution degree: 3, Uncontrolled Environment
Insulation test voltage: 7400 VRMS / 5 s
Connection cable for model without integrator
Type: 3 x 24 AWG shielded
Length: 3 m. Other lengths on request: 5, 7, 10, 15 m
Connection cable for model with integrator
Type: 5 x 24 AWG shielded
Length: 3 m. Other lengths on request: 5, 7, 10, 15 m
Environmental conditions
Protection degree: IP68
Operating temperature: -35 … +75°C up to 2500 A with 15 … 41 cm coil length
-35 … +60°C up to 5000 A with 42 … 50 cm coil length
Standards compliance
IEC, UL standards:
ANSI/CAN/UL 2808, CSA C22.2 NO. 61010-1-12, IEC 61010-2-032,
IEC 61010-1 Ed3, IEC 60529, IEC 61869-10
Certification