Description
DO YOU NEED ADDITIONAL CONFIGURATIONS?
For other configurations contact the sales representative
TECHNICAL SPECIFICATIONS
Coil
Coil length: 30 … 300 cm
Coil diameter: 9.6 … 95.6 cm
Cord diameter: 8.3 ±0.2 mm
Cord material: polyphenylene and thermoplastic elastomers
Fastening: bayonet holder
Weight: 150 … 500 g
Electrical characteristics for model without integrator
Nominal output rate: 120 mV / kA @ 60 Hz (RMS values) – 100 mV / kA @ 50 Hz (RMS values)
Max measurable current: 2 kA @ 50/60 Hz with 30 … 42 cm coil length – 5 kA @ 50/60 Hz with 43 … 300 cm coil length
Coil resistance: 70 … 900 Ω
Accuracy: Class 0,5-A1 according to IEC 61869-10
Frequency: 50/60 Hz
Maximum primary voltage: 600 V CAT IV, Service Entrance
Pollution degree: 2, Controlled Environment for indoor use model – 3, Uncontrolled Environment for outdoor use model
Insulation test voltage: 7400 VRMS / 5 s
Electrical characteristics for model with integrator
Power voltage: 4 … 26 VDC
Max consumption: 5 mADC
Nominal output rate: 333 mV / FS (RMS values) – FS changes according to the model: 1, 2, 5 kA
Positioning error: Better than ±1% of reading
Frequency: 50/60 Hz
Maximum primary voltage: 600 V CAT IV, Service Entrance
Pollution degree: 2, Controlled Environment for indoor use model – 3, Uncontrolled Environment for outdoor use model
Insulation test voltage: 7400 VRMS / 5 s
Connection cable for model without integrator
Type: 3 x 24 AWG shielded
Length: 3 m. Other lengths on request: 5, 7, 10, 15 m
Connection cable for model with integrator
Type: 5 x 24 AWG shielded
Length: 3 m. Other lengths on request: 5, 7, 10, 15 m
Environmental conditions
Protection degree: IP65 for indoor use model – IP68 for outdoor use model
Operating temperature: -35 … +75°C up to 2 kA, -35 … +60°C from 2 to 5 kA
Storage temperature: -40 … +90°C
Standard compliance
IEC, UL standards: ANSI/CAN/UL 2808, CSA C22.2 NO. 61010-1-12, IEC 61010-2-032, IEC 61010-1 Ed3, IEC 60529, IEC 61869-10
Certification